Analog signal types used with the AlarmAgent and how to configure each type

What analog signal types can I use with the AlarmAgent? How do I configure each type?

Using Channels 9 and/or 10 as Analog Inputs:

The factory default is 4 - 20 mA for signal sources. Inputs are single-ended, meaning the common side of each is internally connected to common ground. This means that no other point in the loop should be grounded.

Maybe check their spam folder and allow those emails to come through?

Note: The default configuration for channels 9 & 10 is digital input, alarming on closed circuit. To use analog inputs, the channel(s) must be configured as analog inputs via the web site.

Removing jumper JP8 or JP9 will enable input number 9 or 10 to accept 1 - 5 vdc.